Types of heat pumps



Operation

Main article: Heat pump and refrigeration cycle

According to the second law of thermodynamics heat cannot spontaneously flow from a colder location to a hotter area; work is required to achieve this.

Since the heat pump or refrigerator uses a certain amount of work to move the refrigerant, the amount of energy or btus deposited on the hot side is greater than taken from the cold side.

One common type of heat pump works by exploiting the physical properties of an evaporating and condensing fluid known as a refrigerant.

 

A simple stylized diagram of a heat pump's vapor-compression refrigeration cycle: 1) condenser, 2) expansion valve, 3) evaporator, 4) compressor.

The working fluid, in its gaseous state, is pressurized and circulated through the system by a compressor. On the discharge side of the compressor, the now hot and highly pressurized gas is cooled in a heat exchanger, called a condenser, until it condenses into a high pressure, moderate temperature liquid. The condensed refrigerant then passes through a pressure-lowering device like an expansion valve, capillary tube, or possibly a work-extracting device such as a turbine. This device then passes the low pressure, (almost) liquid refrigerant to another heat exchanger, the evaporator where the refrigerant evaporates into a gas via heat absorption. The refrigerant then returns to the compressor and the cycle is repeated.

In such a system it is essential that the refrigerant reach a sufficiently high temperature when compressed, since the second law of thermodynamics prevents heat from flowing from a cold fluid to a hot heat sink. Practically, this means the refrigerant must reach a temperature greater than the ambient around the high-temperature heat exchanger. Similarly, the fluid must reach a sufficiently low temperature when allowed to expand, or heat cannot flow from the cold region into the fluid, i.e. the fluid must be colder than the ambient around the cold-temperature heat exchanger. In particular, the pressure difference must be great enough for the fluid to condense at the hot side and still evaporate in the lower pressure region at the cold side. The greater the temperature difference, the greater the required pressure difference, and consequently the more energy needed to compress the fluid. Thus as with all heat pumps , the energy efficiency (amount of heat moved per unit of input work required) decreases with increasing temperature difference.

Due to the variations required in temperatures and pressures, many different refrigerants are available. Refrigerators, air conditioners, and some heating systems are common applications that use this technology.



In HVAC applications, a heat pump normally refers to a vapor-compression refrigeration device that includes a reversing valve and optimized heat exchangers so that the direction of heat flow may be reversed. The reversing valve switches the direction of refrigerant through the cycle and therefore the heat pump may deliver either heating or cooling to a building. In the cooler climates the default setting of the reversing valve is heating. The default setting in warmer climates is cooling. Because the two heat exchangers, the condenser and evaporator, must swap functions, they are optimized to perform adequately in both modes. As such, the efficiency of a reversible heat pump is typically slightly less than two separately-optimized machines.

In plumbing applications, a heat pump is sometimes used to heat or preheat water for swimming pools or domestic water heaters.

In somewhat rare applications, both the heat extraction and addition capabilities of a single heat pump can be useful, and typically results in very effective use of the input energy. For example, when an air cooling need can be matched to a water heating load, a single heat pump can serve two useful purposes. Unfortunately, these situations are rare because the demand profiles for heating and cooling are often significantly different.

Refrigerants

Until the 1990s, the refrigerants were often chlorofluorocarbons such as R-12 (dichlorodifluoromethane), one in a class of several refrigerants using the brand name Freon, a trademark of DuPont. Its manufacture was discontinued in 1995 because of the damage that CFCs cause to the ozone layer if released into the atmosphere. One widely-adopted replacement refrigerant is the hydrofluorocarbon (HFC) known as R-134a (1,1,1,2-tetrafluoroethane). R-134a is not as efficient as the R-12 it replaced (in automotive applications) and therefore, more energy is required to operate systems utilizing R-134a than those using R-12. Other substances such as liquid R-717 ammonia are widely used in large-scale systems, or occasionally the less corrosive but more flammable propane or butane, can also be used.

Since 2001, carbon dioxide, R-744, has increasingly been used, utilizing the transcritical cycle. In residential and commercial applications, the hydrochlorofluorocarbon (HCFC) R-22 is still widely used, however, HFC R-410A does not deplete the ozone layer and is being used more frequently. Hydrogen, helium, nitrogen, or plain air is used in the Stirling cycle, providing the maximum number of options in environmentally friendly gases. More recent refrigerators are now exploiting the R600A which is isobutane, and does not deplete the ozone and is friendly to the environment.

Efficiency

When comparing the performance of heat pumps , it is best to avoid the word "efficiency" which has a very specific thermodynamic definition. The term coefficient of performance (COP) is used to describe the ratio of useful heat movement to work input. Most vapor-compression heat pumps utilize electrically powered motors for their work input. However, in most vehicle applications, shaft work, via their internal combustion engines, provide the needed work.

When used for heating a building on a mild day, a typical air-source heat pump has a COP of 3 to 4, whereas a typical electric resistance heater has a COP of 1.0. That is, one joule of electrical energy will cause a resistance heater to produce one joule of useful heat , while under ideal conditions, one joule of electrical energy can cause a heat pump to move much more than one joule of heat from a cooler place to a warmer place.

Note that when there is a wide temperature differential, e.g., when an air-source heat pump is used to heat a house on a very cold winter day, it takes more work to move the same amount of heat indoors than on a mild day. Ultimately, due to Carnot efficiency limits, the heat pump's performance will approach 1.0 as the outdoor-to-indoor temperature difference increases. This typically occurs around −18 C (0 F) outdoor temperature for air source heat pumps . Also, as the heat pump takes heat out of the air, some moisture in the outdoor air may condense and possibly freeze on the outdoor heat exchanger. The system must periodically melt this ice. In other words, when it is extremely cold outside, it is simpler, and wears the machine less, to heat using an electric-resistance heater than to strain an air-source heat pump .

Geothermal heat pumps , on the other hand, are dependent upon the temperature underground, which is "mild" all year round. Their COP is therefore always in the range of 3.54.0.

In cooling mode a heat pump's operating performance is described as its energy efficiency ratio (EER) or seasonal energy efficiency ratio (SEER), and both measures have units of BTU/(hW) (1 BTU/(hW) = 0.293 W/W). A larger EER number indicates better performance. The manufacturer's literature should provide both a COP to describe performance in heating mode and an EER or SEER to describe performance in cooling mode. Actual performance varies, however, and depends on many factors such as installation, temperature differences, site elevation, and maintenance.

Heat pumps are more effective for heating than for cooling if the temperature difference is held equal. This is because the compressor's input energy is largely converted to useful heat when in heating mode, and is discharged along with the moved heat via the condenser. But for cooling, the condenser is normally outdoors, and the compressor's dissipated work is rejected rather than put to a useful purpose.

For the same reason, opening a food refrigerator or freezer heats up the room rather than cooling it because its refrigeration cycle rejects heat to the indoor air. This heat includes the compressor's dissipated work as well as the heat removed from the inside of the appliance.

The COP for a heat pump in a heating or cooling application, with steady-state operation, is:

 


where

ΔQcool is the amount of heat extracted from a cold reservoir at temperature Tcool,

ΔQhot is the amount of heat delivered to a hot reservoir at temperature Thot,

ΔA is the compressor's dissipated work.

All temperatures are absolute temperatures usually measured in kelvins (K).

COP and lift

The COP increases as the temperature difference, or "lift", decreases between heat source and destination. The COP can be maximised at design time by choosing a heating system requiring only a low final water temperature (e.g. underfloor heating), and by choosing a heat source with a high average temperature (e.g. the ground). Domestic hot water (DHW) and radiators require high water temperatures, affecting the choice of heat pump technology.

 

Pump type and source Typical use case COP variation with Output Temperature
35 C (e.g. heated screed floor) 45 C (e.g. heated screed floor) 55 C (e.g. heated timber floor) 65 C (e.g. radiator or DHW) 75 C (e.g. radiator & DHW) 85 C (e.g. radiator & DHW)
High efficiency air source heat pump (ASHP). Air at −20 C   2.2 2.0
Two-stage ASHP air at −20 C Low source temp. 2.4 2.2 1.9
High efficiency ASHP air at 0 C Low output temp. 3.8 2.8 2.2 2.0
Prototype transcritical CO2 (R744) heat pump with tripartite gas cooler, source at 0 C High output temp. 3.3 4.2 3.0
Ground source heat pump (GSHP). Water at 0 C   5.0 3.7 2.9 2.4
GSHP ground at 10 C Low output temp. 7.2 5.0 3.7 2.9 2.4
Theoretical Carnot cycle limit, source −20 C   5.6 4.9 4.4 4.0 3.7 3.4
Theoretical Carnot cycle limit, source 0 C   8.8 7.1 6.0 5.2 4.6 4.2
Theoretical Lorentz cycle limit (CO2 pump), return fluid 25 C, source 0 C   10.1 8.8 7.9 7.1 6.5 6.1
Theoretical Carnot cycle limit, source 10 C   12.3 9.1 7.3 6.1 5.4 4.8

Types of heat pumps

The two main types of heat pumps are compression heat pumps and absorption heat pumps. Compression heat pumps always operate on mechanical energy (through electricity), while absorption heat pumps may also run on heat as an energy source (through electricity or burnable fuels).

A number of sources have been used for the heat source for heating private and communal buildings .

  • air source heat pump (extracts heat from outside air)
    • airair heat pump (transfers heat to inside air)
    • airwater heat pump (transfers heat to a tank of water)
  • geothermal heat pump (extracts heat from the ground or similar sources)
    • geothermalair heat pump (transfers heat to inside air)
      • groundair heat pump (ground as a source of heat)
      • rockair heat pump (rock as a source of heat)
      • waterair heat pump (body of water as a source of heat)
    • geothermalwater heat pump (transfers heat to a tank of water)
      • groundwater heat pump (ground as a source of heat)
      • rockwater heat pump (rock as a source of heat)
      • waterwater heat pump (body of water as a source of heat)

Heat sources

Most commonly, heat pumps draw heat from the air (outside or inside air) or from the ground (groundwater or soil) . The heat drawn from the ground is in most cases stored solar heat, and it should not be confused with geothermal heat, though the latter will contribute in some small measure to all heat in the ground. Other heat sources include water; nearby streams and other natural water bodies have been used, and sometimes domestic waste water which is often warmer than the ambient temperature.